EP-LS Series 2
Our Products / Emergency Power Packs / EP-LS Series 2
EP-LS Series 2
The EP-LS2 emergency power pack with transfer relay is compactly designed, perfect for hidden installations in the ceiling to provide power for emergency lights installed in or under the ceiling. The EP-LS2 Power Pack is equipped with an innovative 3 Steps Charger (patent number 15955) to help extend the operational life of the battery.
The casing is produced from 1mm thick Electro-Galvanized steel coated with Epoxy powder and special chemicals to prevent any possible rust. The EP-LS2 emergency power pack has undergone continued innovation to give maximum value and functions to the users, as can be seen in the feature list.
Technical Specifications
Mode of Operation | Non-Maintained |
Operation Temperature | 0-40°C |
Input Voltage | Operating Line 230VAC / 50Hz |
Battery Type / Capacity | Lithium Iron Phosphate (LiFePO4)
12.8V – 4Ah |
Protection Features | – AC, DC Fuse
– Surge Protection |
Testing System | Auto Test |
Output Voltage | 12VDC ± 18% (Non – Maintained) |
Backup Time | |
Total Maximum Load | 36W |
Charging period | 10-15 Hrs. |
Housing | Electro-galvanized steel sheet 1mm. thick with epoxy powder coating. |
Dimensions (LxWxH) | 220 x 70 x 73 mm
|
Weight | 1.29 Kg |
IP Rating | IP20 |
Mounting | Ceiling Concealed |
Wiring Diagram
Features
Supported Load
- A 12 Vdc±18% load for emergency lamps
Battery
- Lithium Iron Phosphate (LiFePO4) 12.8V-4Ah
Power Supply Duration
Functions
- An automatic 30-minute test can be set to perform every 30 days. This automatic testing can be turned on or off.
Circuit Sytems
- Controlled by an 8 bit microcontroller circuit.
- An Autoactivation circuit when under voltage occurs.
- A Timer Delay circuit to keep the unit operating for a few more seconds once normal power has returned.
Protection Features
- AC and DC fuse to prevent current overload.
- Surge Protection.
Features to Extend Battery Life
- An innovative 3 Steps Charger (Limit Current, Constant Voltage, Flip-Flop Charger).
- A Low Voltage Cut-Off to prevent the battery from draining completely.
Warning Systems
- An audible alarm will sound once every 15 seconds to warn that the Low Voltage Cut-Off is about to activate.
- An audible alarm will sound twice every 15 seconds to indicate that the battery should be charged.
- An LED will blink 3 times every 15 seconds to warn that there is less than 30 minutes of charge left in the battery. This warning will show for 10 minutes.
- An LED will blink 4 times every 15 seconds to warn that there is a problem charging the battery. This warning will show for 10 minutes
EP-LS Series 2 | Spec Sheets
Model | Battery Capacity | Back up (hr.) | Length (mm) | Width (mm) | Height (mm) | Weight (kgs.) |
---|---|---|---|---|---|---|
EP-LS2 | 12.8V – 4Ah | 1.15-4.30 | 220 | 70 | 73 | 1.29 |